TY - JOUR
T1 - Water-energy tradeoffs in data centers
T2 - A case study in hot-arid climates
AU - Karimi, Leila
AU - Yacuel, Leeann
AU - Johnson, Joseph Degraft
AU - Ashby, Jamie
AU - Green, Michael
AU - Renner, Matt
AU - Bergman, Aryn
AU - Norwood, Robert
AU - Hickenbottom, Kerri L.
N1 - Publisher Copyright:
© 2022 Elsevier B.V.
PY - 2022/6
Y1 - 2022/6
N2 - Although energy and water are intertwined, the analysis of energy consumption in data centers (DCs) has largely ignored water needs. In this study, we utilize established DC efficiency metrics, power usage effectiveness (PUE) and water usage effectiveness (WUE), to analyze the water and energy use in two colocation DCs (DC1 and DC2) located in the greater Phoenix area. These DCs use distinct cooling systems: DC1 uses air-cooled chillers and DC2 uses both water-cooled chillers and evaporative cooling. We also present a method for analyzing the water-energy tradeoff in DCs as a useful tool for DC designers and managers to evaluate different cooling systems. The results highlight that although DC1’s average PUE is nearly 13% higher compared to DC2's average PUE, its source WUE is 66% lower than DC2. In addition, DC1’s PUE is more affected by seasonal changes (variation of dry-bulb temperature), while DC2's WUE has a larger seasonal variation. Our cooling system analysis indicates that hybrid evaporative cooling has the least power consumption, while air-cooled chillers have the most water use. Utilizing free cooling and evaporative cooling when outside air condition permits (∼40% per year), results in substantial power and water savings in Phoenix DCs.
AB - Although energy and water are intertwined, the analysis of energy consumption in data centers (DCs) has largely ignored water needs. In this study, we utilize established DC efficiency metrics, power usage effectiveness (PUE) and water usage effectiveness (WUE), to analyze the water and energy use in two colocation DCs (DC1 and DC2) located in the greater Phoenix area. These DCs use distinct cooling systems: DC1 uses air-cooled chillers and DC2 uses both water-cooled chillers and evaporative cooling. We also present a method for analyzing the water-energy tradeoff in DCs as a useful tool for DC designers and managers to evaluate different cooling systems. The results highlight that although DC1’s average PUE is nearly 13% higher compared to DC2's average PUE, its source WUE is 66% lower than DC2. In addition, DC1’s PUE is more affected by seasonal changes (variation of dry-bulb temperature), while DC2's WUE has a larger seasonal variation. Our cooling system analysis indicates that hybrid evaporative cooling has the least power consumption, while air-cooled chillers have the most water use. Utilizing free cooling and evaporative cooling when outside air condition permits (∼40% per year), results in substantial power and water savings in Phoenix DCs.
KW - Building energy analysis
KW - Data centers
KW - Energy efficiency
KW - Sustainable infrastructure
KW - Water conservation
KW - Water-energy nexus
UR - http://www.scopus.com/inward/record.url?scp=85124824134&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=85124824134&partnerID=8YFLogxK
U2 - 10.1016/j.resconrec.2022.106194
DO - 10.1016/j.resconrec.2022.106194
M3 - Article
AN - SCOPUS:85124824134
SN - 0921-3449
VL - 181
JO - Resources, Conservation and Recycling
JF - Resources, Conservation and Recycling
M1 - 106194
ER -